Manuals Industrial Range

X42 Monitoring

XMC-Fire — Fire Tank Monitoring HMI
User Manual

Installation · Commissioning · Configuration · Fault Finding

Audience: field technicians · x42monitoring.com

DOCUMENT STATUS: FRAMEWORK — DRAFT ONLY. Not for issue. All amber-highlighted placeholder items must be completed with hardware specifications and site-specific details before this manual is issued to technicians. Remove this banner before publishing.

Read this manual before installing or operating the device. Keep it with the equipment.

Contents

Document control

Field Detail
Document title XMC-Fire User Manual
Document number [PLACEHOLDER] — doc number
Revision [PLACEHOLDER] — e.g. Rev A
Issue date [PLACEHOLDER]
Applies to firmware [PLACEHOLDER] — version / range
Applies to hardware [PLACEHOLDER] — model / variant codes
Prepared by [PLACEHOLDER]
Approved by [PLACEHOLDER]
Manufacturer Kangaroo Kick Tech Pty Ltd trading as X42 Monitoring, ABN 66 679 196 073, Queensland, Australia

Revision history

Rev Date Description Author
A [PLACEHOLDER] First issue [PLACEHOLDER]
       

About this manual

This manual covers installation, commissioning, configuration, and fault finding for the XMC-Fire HMI device. Steps are written for technicians who are familiar with industrial instrumentation and networking but who may not have worked with this device before.

Intended users

Installation, commissioning and servicing must be carried out only by a competent person: a technician with training, qualifications or experience in industrial instrumentation, low-voltage wiring and, where the device is connected to a fire protection system, the applicable fire protection service requirements.

✎ PLACEHOLDER — confirm licensing / competency wording with your compliance adviser

Intended use

The XMC-Fire is intended for monitoring and signalling of water level in fire tanks and similar industrial storage vessels, and for transmitting that data to building management, SCADA and cloud systems. Any other use is outside the intended use of the product.

✎ PLACEHOLDER — state explicitly what the device is NOT — e.g. not a certified fire detection or alarm device under AS 1670, not a substitute for the routine service required by AS 1851

Safety notices used in this manual

Safety messages in this manual use the following signal words. Read and obey every safety message.

Signal word Meaning
DANGER Hazardous situation that, if not avoided, will result in death or serious injury.
WARNING Hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION Hazardous situation that, if not avoided, could result in minor or moderate injury.
NOTICE Practice not related to personal injury: risk of equipment damage, data loss or process upset.
NOTE Additional information that helps avoid a common mistake or improves the result.
⚠  WARNING
Example only. Replace with the real hazard statements identified by the product risk assessment. Each safety message must state the hazard, the consequence of ignoring it, and how to avoid it.

Related documents and standards

  • XMD remote display user manual — [PLACEHOLDER] — document number
  • XMC-Fire hardware datasheet — [PLACEHOLDER]
  • Sensor manufacturer instructions — [PLACEHOLDER]
  • AS 1851 Routine service of fire protection systems and equipment — service and record-keeping obligations for the tank the device monitors
  • IEC/IEEE 82079-1 Preparation of information for use — structure and content of this manual

1 Overview

1.1 What the XMC-Fire does

The XMC-Fire is designed for monitoring fire tank water reserves for commercial and high-rise buildings, as a one-stop solution for buildings to meet the monitoring and service requirements of the fire protection codes.

It monitors up to two 4–20 mA current loop level sensors, displays live values on its built-in touchscreen, and sends data to a third-party cloud platform via WiFi and MQTT. Data can be shared with BMS and SCADA systems through the Modbus TCP protocol, through auxiliary signalling analogue outputs (0–10 V), and through voltage-free relay outputs driven by configurable alarm thresholds.

The XMC-Fire connects to XMD rugged remote display units, or can act as a high-end auxiliary display itself. Local trending of level readings over 50 days assists service, maintenance and troubleshooting.

1.2 Key features at a glance

  • Touchscreen HMI with live sensor display and trend graphs
  • 2 × 4–20 mA analogue sensor inputs (configurable as hydrostatic or radar)
  • 2 × digital inputs
  • 6 × relay outputs and 2 × analogue outputs
  • WiFi connectivity with MQTT data publishing
  • Modbus TCP (read-only, over WiFi) and Modbus RTU (RS-485)
  • Remote display link — drives up to 4 external displays, or acts as a remote display itself (single or dual channel)
  • FRAM non-volatile storage for configuration and trend history
  • Status LED visible at distance

1.3 Device identification

Item Where to find it / format
Device name Set on the Interface screen; used in the MQTT topic path
Client ID X42_XMC_{Unit ID} — shown on the About screen

2 Installation

2.1 Mechanical

✎ PLACEHOLDER — panel cut-out dimensions, mounting torque, IP rating, minimum clearances, orientation

2.2 Wiring

Power supply

✎ PLACEHOLDER — voltage range, current draw, terminal numbers, protective earth, fusing
⚠  WARNING
The 24 V supply is monitored. Operating below the minimum voltage triggers a Low Supply warning and, if it falls further, a brownout shutdown to protect the configuration data.
Ensure the supply is adequately sized for the device and all connected loads.

Analogue inputs (Loop 1 and Loop 2)

Signal type: 4–20 mA current loop.

✎ PLACEHOLDER — terminal numbers, loop power (active / passive), maximum loop resistance

Sensor range check: the device flags a sensor fault if the loop current falls outside 3.7 mA – 20.3 mA. See Section 11.

Digital inputs

✎ PLACEHOLDER — terminal numbers, voltage level, wet / dry contact

Relay outputs (RL1 – RL6)

✎ PLACEHOLDER — contact rating, terminal numbers, NO / NC / COM

Analogue outputs (AO1, AO2)

✎ PLACEHOLDER — signal type (4–20 mA / 0–10 V), terminal numbers, maximum load impedance

RS-485 (Modbus RTU)

✎ PLACEHOLDER — terminal numbers, termination requirements, cable type

Used for the remote display link. See Section 9.4.

Grounding and shielding

✎ PLACEHOLDER — earthing and screen termination practice

3 First power-on and startup

3.1 Startup sequence

  1. Apply power. The splash screen appears for a few seconds.
  2. The device transitions to the Main Screen (Home Multi).
  3. The Status LED shows GREEN solid when all is healthy. If it is ORANGE or RED on first startup, refer to Section 5.

3.2 Factory / test mode

A new or factory-reset device starts in factory mode (flag PARAM_FLAG_FACTORY_MODE_OFF = 0). Normal operation begins once the flag is set.

✎ PLACEHOLDER — describe what is locked out in factory mode, and the action that clears it — e.g. “Set the admin password on the Security screen to exit factory mode”

3.3 Setting the admin password (first login)

✎ PLACEHOLDER — walk through the Security screen steps to set the password and confirm PARAM_FLAG_CREDS_SET is saved

3.4 WiFi commissioning

✎ PLACEHOLDER — open the Interface screen, enter SSID and password, save; the device reconnects automatically

3.5 Setting the clock

The device synchronises time automatically via NTP (pool.ntp.org) once WiFi is connected. No manual time entry is required.

NOTE
If WiFi is not used, the internal clock will not be set. Trend timestamps will be inaccurate until a sync occurs.

4 Main screen guide (Home Multi)

4.1 Pages

The main screen has up to three swipeable pages. The active page is selected automatically based on which sensors are enabled, but can be swiped manually.

Page View Shown when
Page 0 Dual view — both sensors side by side with individual trend graphs Both sensors enabled
Page 1 Sensor 1 large view — full screen with trend graph Only Sensor 1 enabled
Page 2 Sensor 2 large view — full screen with trend graph Only Sensor 2 enabled
NOTE
When the device is set to Remote Display mode (Slave), swipe is locked. Page 0 is used for Dual Display mode and Page 1 for Single Display mode. See Section 9.4.

4.2 Value displays

Each sensor panel shows:

  • Live value in engineering units, with the label set in Sensor Configuration
  • Minimum and maximum indicators
  • A status indicator if the sensor is in fault

4.3 Trend graph

The graph scrolls as new samples arrive (one sample every 12 hours). The horizontal axis represents time, oldest on the left. History is loaded from memory when the screen is first shown. To clear the trend history, go to Settings > Device Configuration.

4.4 Info bar (top of screen)

Updated approximately every 10 display frames.

Indicator Meaning
WiFi signal bars No bars = disconnected or not configured; 1 bar = very weak (below −100 dBm); 2 bars = weak (−100 to −80 dBm); 3 bars = fair (−80 to −60 dBm); 4 bars = good (−60 to −40 dBm); 5 bars = strong (−40 dBm and above)
IP address Assigned by DHCP. Used for Modbus TCP access.
Board temperature Ambient temperature inside the enclosure. Shows “--.-” if outside −20 to 100 °C.
TCP indicator Lit when a Modbus TCP client is connected.
Remote count Number of remote displays currently linked. Shows “R” when this device is acting as a remote display.
Relay status Two short text fields showing the state of the configured relay outputs.

4.5 System status indicators

Indicator Condition
SYS System-level fault — software fault or hardware reset required
LOW SUPPLY Supply voltage below threshold
CRITICAL Brownout — outputs have been de-energised to protect data
ALARM One or more alarm thresholds active
AUTO DIM Display auto-dimming is active

5 Status indicators

5.1 Status LED

The LED on the front panel reflects the current health of the device.

LED state Meaning
GREEN solid Normal — no active faults or warnings
GREEN fast flash Information event active (non-urgent)
ORANGE solid Warning active (communications, power threshold)
ORANGE slow flash Warning is clearing / recovering
RED solid Fault active (sensor out of range, power brownout, FRAM error)
RED slow flash Fault is clearing / recovering

5.2 Screen indicators

The Home Multi screen also shows system status icons. See Section 4.

5.3 What to do when the LED is not green

Check the Commissioning screen for live readings and relay states. If faults persist, refer to Section 11 (Fault Finding) and Appendix A (Error Code Table).

6 Settings menu guide

6.0 Accessing settings

From the Main Screen, press the Settings button. If an admin password has been set, you are prompted for it first.

✎ PLACEHOLDER — default password — state it here and instruct the technician to change it on first use

6.1 Device configuration

Display auto-on (LDR)

Setting Description
Enable On / Off
ON threshold LDR reading above which the display turns on
OFF hysteresis LDR reading must fall this far below the ON threshold before the display turns off
Brightness LCD backlight level

Display forced on (digital input / fire alarm input)

Setting Description
Enable On / Off
Min on-time Seconds the display stays on after the input clears, to avoid rapid on/off flickering

Trend history

  • Clear Sensor 1 trend — wipes stored trend data for Channel 1
  • Clear Sensor 2 trend — wipes stored trend data for Channel 2
NOTICE
Clearing trend data cannot be undone. Export or record any data required for service evidence before clearing.

6.2 Sensor configuration

Applies separately to Sensor 1 and Sensor 2.

Setting Description
Enable On / Off
Name Up to 10 characters, shown on the main screen
Sensor type Hydrostatic — pressure-based level sensor; Radar — distance / time-of-flight sensor
Full-scale range Maximum measurable distance or depth (mm)
Full level Distance or depth at 100 % fill (mm)
Empty level Distance or depth at 0 % fill (mm)
Install height Height of sensor above vessel bottom (mm). Required for radar sensors. Must be greater than the Full level value.
Offset (software trim) Added to the raw reading after scaling, in engineering units
Gain (software trim) Multiplier applied to the raw reading
NOTE
After changing sensor configuration, check that the main screen value matches a known reference measurement before relying on alarms.

6.3 Alarm settings

Up to 6 independent alarm thresholds are available.

Setting Description
Name Up to 10 characters
Source Which sensor or data point drives this alarm
Activate at Threshold to turn the alarm ON
Deactivate at Threshold to turn the alarm OFF (hysteresis)
Min active time Alarm stays on for at least this many seconds, preventing rapid cycling
Output Which relay this alarm drives
Override Auto — alarm controls the relay normally; Force On — relay held on regardless of process value; Force Off — relay held off regardless of process value
NOTE
If the Activate threshold is set lower than the Deactivate threshold, the logic is inverted — the alarm triggers when the value falls below the threshold rather than rises above it. This is useful for low-level alarms.

6.4 Interface (WiFi, MQTT, Modbus TCP)

WiFi

Setting Description
SSID Network name, up to 20 characters
Password Network password, up to 20 characters
NOTE
Saving triggers an automatic reconnect attempt.

MQTT

Setting Description
Broker Hostname or IP address of the MQTT broker, up to 32 characters
Port Default 1883 (plain) or 8883 (TLS)
TLS On / Off
Clean session On / Off
QoS 0, 1 or 2
Keepalive Keepalive interval in seconds
Client ID Override the auto-generated ID (optional, up to 32 characters)
Username MQTT broker username, up to 32 characters
Password MQTT broker password, up to 32 characters

Modbus TCP

Setting Description
Slave address This device’s address on the Modbus network (1–247)
Port TCP port to listen on (default 502)
IP address This device’s IP address
NOTE
Modbus TCP is read-only. Remote writes are not supported.

6.5 Security (admin password)

Enter the new password twice to confirm. Once set, this password is required to enter Settings.

✎ PLACEHOLDER — minimum length — CREDENTIALMINIMUMLENGTH characters
NOTICE
If you forget the admin password, a factory reset is required to regain access, and all site configuration is lost. Record the password in a secure location.

6.6 Remote display (Modbus RTU mode)

Mode Behaviour
Master — Send to remote displays This device polls up to 4 remote display units and sends them values from its configured data slots.
Slave — Single display This device acts as a remote display, receiving one channel from a master device.
Slave — Dual display This device acts as a remote display, receiving two channels.
Slave address This device’s address when operating as a slave (1–247)

Remote device configuration (Master mode only, up to 4 devices)

Setting Description
Address Slave address of the remote display (1–247)
Enable On / Off
Slots 1–7 Each slot can read or write one Modbus register
Function code 3 = Read Holding, 4 = Read Input, 6 = Write Register
Register Starting register address
Count / value Register count (reads) or write value
NOTICE
Changing the Modbus RTU mode requires the device to reboot. Save changes, then confirm the reboot when prompted.

6.7 Commissioning

For use during installation and fault finding. Not for normal operation.

Live readings

  • 24 V supply rail voltage
  • Loop 1 raw current (mA) — useful for verifying sensor wiring
  • Loop 2 raw current (mA)

Relay override controls

Each of the 6 relays can be set to Auto (controlled by alarm logic), Force On (energised regardless of process value) or Force Off (de-energised regardless of process value).

⚠  WARNING
Force overrides bypass all alarm logic. While an override is active the device will not signal a genuine low-level condition.
Return all relays to Auto and verify normal operation before leaving the site.

Suspend actions

Pauses Modbus master polling and MQTT publishing while enabled. Use when making wiring changes that would otherwise cause spurious alarms.

Display test

Sends a test pattern to all connected remote displays. Use to verify the RS-485 wiring to remote display units.

6.8 About

Read-only device information:

  • Device name — as configured on the Interface screen
  • Firmware version
  • MAC address
  • Unit ID (serial)

7 Inputs and outputs

7.1 Analogue inputs

Two 4–20 mA current loop inputs (Loop 1, Loop 2). Each input is independently configurable — see Section 6.2.

Fault detection

The device monitors each loop current continuously. A fault is logged and the LED turns RED if the current falls outside:

  • Low limit: 3.7 mA (below 4 mA — open circuit or sensor failure)
  • High limit: 20.3 mA (above 20 mA — short circuit or sensor overrange)
NOTE
The sensor fault flags are available in the MQTT payload (SEC field) and via Modbus registers. See Appendix B and Appendix C.

7.2 Digital inputs

Two digital inputs (DIG_INPUT_1, DIG_INPUT_2).

✎ PLACEHOLDER — voltage levels, active high / low, typical use cases

One use case is Display Force-On: digital input 1 can be configured to force the touchscreen on when asserted, for example from a fire alarm panel. See Section 6.1.

7.3 Relay outputs

Six relay outputs (RL1 – RL6). Each relay is driven by one of the 6 configurable alarm thresholds. Relays can also be forced manually from the Commissioning screen.

⚠  WARNING
In a power brownout (supply critically low) all relays are de-energised to protect stored configuration data. Once the supply recovers, normal alarm logic resumes.
Ensure fail-safe wiring conventions are followed for critical outputs.

7.4 Analogue outputs

Two analogue outputs (AO1, AO2).

✎ PLACEHOLDER — signal range, resolution, typical use — retransmission of sensor value to a PLC or recorder
NOTICE
Analogue outputs are also set to a safe state (zero / minimum) during a power brownout.

8 Alarms

The device provides 6 independent alarm channels. Each alarm monitors a selected data point and activates a relay when the threshold conditions are met.

8.1 Normal (high) alarm

  • Activate threshold < Deactivate threshold
  • Alarm ON when the value rises above the Activate threshold
  • Alarm OFF when the value falls below the Deactivate threshold

8.2 Inverted (low) alarm

  • Activate threshold > Deactivate threshold (set Activate lower)
  • Alarm ON when the value falls below the Activate threshold
  • Alarm OFF when the value rises above the Deactivate threshold

8.3 Minimum active time

Prevents the relay from de-energising immediately after the process value crosses the Deactivate threshold. Useful for pump protection and for avoiding rapid cycling.

8.4 Relay override

See Section 6.7 for manual force control via the Commissioning screen.

⚠  WARNING
Return all overrides to Auto after commissioning. An alarm relay left in Force Off will not signal a genuine fault condition.

9 Communications

9.1 WiFi

The device connects to a standard 2.4 GHz WiFi access point. Configure the SSID and password in Settings > Interface. The IP address is assigned by DHCP and displayed in the Info Bar.

WiFi is required for MQTT data publishing, Modbus TCP access, and NTP time synchronisation.

WiFi can be disabled via the PARAM_FLAG_WIFI_DISABLE flag, set during manufacture for units without the WiFi option. No WiFi errors are reported when disabled.

9.2 MQTT

The device publishes sensor data to an MQTT broker at the interval set in the Posting_sec parameter (default 60 seconds).

Publishing is suppressed when the device is not connected to WiFi or the broker, is in a brownout or safe state, or has actions suspended from the Commissioning screen. For payload details see Appendix C.

Item Value
Topic {device_name}/{MAC_no_colons}/
Example FireX42/AABBCCDDEEFF/
Settings Section 6.4
Status Info Bar WiFi signal bars and LED colour

9.3 Modbus TCP

The device operates as a Modbus TCP slave (server). External SCADA or PLC systems can read register values over the WiFi network. Default port 502, configurable in Settings > Interface. For the register map see Appendix B.

NOTE
Ensure the WiFi access point assigns a consistent (reserved or static) IP address to this device if Modbus TCP SCADA access is required.
NOTE
Modbus TCP is currently read-only. Write commands from external systems are not processed.

9.4 Modbus RTU (remote display link, RS-485)

The RS-485 port supports three operating modes, selected in Settings > Remote Display. A reboot is required when changing mode.

Mode Behaviour
Master — Send to remote displays Polls up to 4 remote display units. Each remote unit has an independent slave address and up to 7 register slots that can be read or written on each poll cycle.
Slave — Single display The device acts as a remote display, showing the value received from a master device on the main screen. Swipe is locked to Page 1 (Sensor 1 large view). A comms loss alarm is raised if no update is received for 30 seconds.
Slave — Dual display As above, but the device receives two channels. Swipe is locked to Page 0 (dual view).
NOTE
RS-485 cable termination and bias resistors follow standard practice.
✎ PLACEHOLDER — site-specific RS-485 guidance if required

10 Trending

The device stores a long-term trend history for both sensor inputs. One sample is recorded every 12 hours.

The trend graph on the main screen displays this history. The oldest samples scroll off the left as new ones are added. Trend data survives power cycles, stored in FRAM non-volatile memory.

To clear the trend history: Settings > Device Configuration > Clear Sensor 1 trend / Clear Sensor 2 trend.

NOTICE
Clearing is permanent and cannot be undone.

11 Fault finding

11.1 LED is ORANGE — warning

  • WiFi connected? Check the SSID and password in Settings > Interface.
  • MQTT connected? Check the broker address and port.
  • Modbus RTU comms: check RS-485 wiring and slave addresses.
  • Supply voltage: is the 24 V supply within specification?

11.2 LED is RED — fault

  • Sensor loop current: go to the Commissioning screen. Loop 1 and Loop 2 raw readings should be between 4 mA and 20 mA. If outside this range, check sensor wiring and sensor health.
  • Supply voltage: a brownout (below the critical threshold) de-energises all outputs. Check the supply.
  • FRAM error: configuration storage fault.
✎ PLACEHOLDER — FRAM recovery steps — e.g. attempt factory restore per Appendix D

11.3 Main screen shows “--.-” for temperature

The board temperature sensor is reading outside −20 to 100 °C. Check the enclosure environment and ambient conditions.

11.4 Remote display count shows “R”

The device is in Slave mode and is acting as a remote display. If this is not intended, change the mode in Settings > Remote Display.

11.5 No trend history visible

  • The trend may have been cleared. History builds up at 12-hour intervals.
  • Alternatively, the device clock was not set (no NTP sync) and samples are being stored with epoch timestamp 0.

11.6 Device not responding to Modbus TCP

  • Check WiFi is connected and the IP address is shown in the Info Bar.
  • Confirm the SCADA system is using the correct IP and port (default 502).
  • Modbus TCP is read-only; confirm the SCADA is not issuing write commands.

11.7 Display not turning on automatically

  • Check Settings > Device Configuration: auto-on must be enabled.
  • Check the LDR threshold setting against the actual ambient light level.
  • Check that a forced-on digital input is not being confused with LDR control.

12 Specifications quick reference

✎ PLACEHOLDER — compile from the hardware datasheet
Parameter Value
Supply voltage [PLACEHOLDER] — V dc, range
Analogue input range 4–20 mA
Sensor fault thresholds Low 3.7 mA / High 20.3 mA
Digital input voltage [PLACEHOLDER] — V, active level
Relay contacts [PLACEHOLDER] — rating, type
Analogue outputs [PLACEHOLDER] — signal type, range
RS-485 [PLACEHOLDER] — baud rates, default
WiFi standard 2.4 GHz, [PLACEHOLDER] — protocol
Operating temperature [PLACEHOLDER] — range °C
Enclosure [PLACEHOLDER] — IP rating, material
Dimensions [PLACEHOLDER] — mm

Appendix A Error code table

Code Name Severity Description / typical cause
0x01 POWER_BROWNOUT Fault Supply voltage critically low. All outputs de-energised. Check supply and cabling.
0x02 SENSOR1_RANGE Fault Loop 1 current outside 3.7–20.3 mA. Check sensor, loop wiring, power.
0x03 SENSOR2_RANGE Fault Loop 2 current outside 3.7–20.3 mA.
0x04 FRAM_CORRUPT Fault NV configuration data integrity failure. See Appendix D.
0x05 FRAM_IO Fault Communication failure with NV storage device. Hardware fault.
0x10 WIFI_DOWN Warning WiFi disconnected. Check SSID, password, access point.
0x11 MQTT_DOWN Warning MQTT broker unreachable or rejected. Check broker address, port, credentials.
0x12 MODBUS_TCP Warning Modbus TCP transport error.
0x13 MODBUS_RTU_SLAVE1 Warning Remote display 1 not responding. Check RS-485 wiring and address.
0x14 MODBUS_RTU_SLAVE2 Warning Remote display 2 not responding.
0x15 MODBUS_RTU_SLAVE3 Warning Remote display 3 not responding.
0x16 MODBUS_RTU_SLAVE4 Warning Remote display 4 not responding.
0x17 POWER_LOW_SUPPLY Warning Supply voltage below low threshold. Outputs still active. Check supply.
0x18 MB_DISPLAY_CH1 Warning Slave mode: no update received on channel 1 for more than 30 s. Check master.
0x19 MB_DISPLAY_CH2 Warning Slave mode: no update on channel 2.

Appendix B Modbus register map summary

Access via Modbus TCP (port 502 default) or Modbus RTU RS-485. The slave address is configured in Settings > Interface.

B.1 Scaling

Float and 32-bit values are scaled to fit a 16-bit register.

Value Scaling Example
Sensor values (AI_EXT_1/2) register = engineering value × 100 12.34 m = 1234
Analogue outputs (AO1/2) register = output value × 100 —
Loop current (IR5 / IR6) register = µA 12000 = 12.000 mA
Thermistor (IR2) register = °C × 100 23.50 °C = 2350
24 V supply (IR3) register = volts × 100 24.10 V = 2410

B.2 Input registers — FC4 Read Input Registers (read-only)

Reg Name Scale Description
IR0 Sensor 1 (AI Ext 1) ×100 External analogue input 1, engineering units
IR1 Sensor 2 (AI Ext 2) ×100 External analogue input 2, engineering units
IR2 Board temperature ×100 Internal thermistor (°C)
IR3 24 V supply rail ×100 Supply voltage (V)
IR4 LDR light level ×1 Raw light sensor reading (display auto-dim)
IR5 Loop 1 current µA Sensor 1 raw loop current (fault range 3700–20300)
IR6 Loop 2 current µA Sensor 2 raw loop current
IR7 Analogue output 1 ×100 AO1 current output value
IR8 Analogue output 2 ×100 AO2 current output value
IR9 System state ×1 0 = Operational, 1 = Degraded, 2 = Safe, 3 = Shutdown, 4 = Fault
IR10 Remote value 1 ×100 Modbus remote input 1 (slave mode: received from master)
IR11 Remote value 2 ×100 Modbus remote input 2 (slave mode: received from master)

B.3 Input bit registers — FC2 Read Discrete Inputs (read-only)

Reg Bit Name Description
IB0 0 Digital input 1 State of digital input 1 (0 = off, 1 = on)
IB0 1 Digital input 2 State of digital input 2 (0 = off, 1 = on)

B.4 Coil registers — FC1 Read Coils / FC5 Write Single Coil

Coil register 0: WRITE — relay force commands from SCADA. Coil register 1: READ — relay actual state read-back.

Reg Bit Name Access Description
CR0 0–5 Relay 1–6 R/W Write 1 to force relay ON, 0 to force OFF
CR1 0–5 Relay 1–6 R Actual relay state (reflects alarm and force logic)
⚠  WARNING
Relay write commands via Modbus are force overrides and bypass alarm logic. The Commissioning screen shows the same force state.
Return coils to 0 or manage via alarm logic for normal operation.
NOTE
Relay write commands are blocked when the device is in Safe State or higher (brownout condition). Coil 0 write commands for ON are also blocked in the Degraded state.

B.5 Holding registers — FC3 Read / FC6 Write Single Register

These registers allow a SCADA system to update alarm thresholds remotely. Changes are saved to non-volatile memory automatically.

Reg Alarm Access Description
HR0 Alarm 1 (RL1) R/W Activate threshold (alarm turns ON above this)
HR1 Alarm 1 (RL1) R/W Deactivate threshold (alarm turns OFF below this)
HR2 Alarm 3 (RL3) R/W Activate threshold
HR3 Alarm 3 (RL3) R/W Deactivate threshold
HR4 Alarm 4 (RL4) R/W Activate threshold
HR5 Alarm 4 (RL4) R/W Deactivate threshold
HR6 Alarm 6 (RL6) R/W Activate threshold
HR7 Alarm 6 (RL6) R/W Deactivate threshold
HR8 AO1 setpoint R/W Analogue output 1 forced value (×100)
HR9 AO2 setpoint R/W Analogue output 2 forced value (×100)
NOTE
Alarms 2 and 5 (RL2, RL5) thresholds are not currently exposed via Modbus holding registers. Configure these via the touchscreen only. Threshold values use the same engineering unit scaling as the sensor input register (×100). Match the scale to your sensor configuration.

B.6 RTU slave mode — display receive registers

When operating as a remote display (Slave Single or Slave Dual mode), the device listens on the RS-485 bus for write commands from the master.

Reg Name Description
HR0 Display channel 1 Written by master — shown as Sensor 1 on the main screen
HR1 Display channel 2 Written by master — shown as Sensor 2 on the main screen (Slave Dual mode only)

Values are sign-extended 16-bit integers. The master should scale values ×100 before writing, matching the sensor display format.

Appendix C MQTT payload reference

C.1 Payload format (JSON)

{ "SIGNAL": { "TS": <timestamp, Unix epoch seconds>, "Tank1": <Sensor 1 value, float, 2 dp>, "Tank2": <Sensor 2 value, float, 2 dp>, "LDR": <light sensor raw reading, integer>, "Temp": <board temperature °C, float, 2 dp>, "DI1": <digital input 1 state, 0 or 1>, "DI2": <digital input 2 state, 0 or 1>, "SEC": <sensor error code bitmask, integer>, "EXT1": <Modbus remote value 1, float, 2 dp>, "EXT2": <Modbus remote value 2, float, 2 dp> } }
Item Value
Topic {device_name}/{MAC_no_colons}/
QoS As configured (0, 1 or 2)
Retain Off
Interval Posting_sec (default 60 s, suspended if not operational)
Subscribe topic (inbound settings) {device_name}/{MAC_no_colons}/Settings/#

C.2 SEC field — sensor error bitmask

Value Meaning
Bit 0 Sensor 1 out of range
Bit 1 Sensor 2 out of range
0 No sensor errors
NOTE
The DA16200 WiFi module firmware v3.3.0 contains a known bug with the MQTT retain flag. This has been corrected in the patched firmware version used in production units (v3.3.0_2).

Appendix D Factory default restoration

✎ PLACEHOLDER — procedure for restoring factory defaults

Considerations to cover when this section is written:

  • Restoration erases all site configuration — WiFi, MQTT, alarms, sensor calibration.
  • Record all settings before proceeding.
  • May require physical access to the device (button sequence or menu option).
  • PARAM_FLAG_FACTORY_MODE_OFF_BIT is cleared — the device returns to factory / test mode and must be recommissioned.
⚠  WARNING
A factory reset returns all alarm relays to their default state. The monitored asset is unsupervised until the device has been fully recommissioned and verified.
Notify the responsible person before resetting a device connected to a fire protection system.

Copyright

X42 Monitoring™. No part of this technical manual may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of X42 Monitoring™.

Disclaimer

✎ PLACEHOLDER — align with the X42 Tank manual disclaimer, adjusted for an industrial / fire application — including the statement that the device does not replace the routine service and record keeping required under AS 1851

Warranty and liability

✎ PLACEHOLDER — Australian Consumer Law statement, warranty period, exclusions — mirror the X42 Tank manual structure

Regulatory information

✎ PLACEHOLDER — RCM / EMC compliance statement, WiFi module radio compliance

Disposal

✎ PLACEHOLDER — end-of-life and e-waste disposal statement

Support and contact

Need help with your XMC-Fire?

Technical advice and resources, including manuals, user instructions and datasheets, are available from x42monitoring.com.
For direct product support email support@x42monitoring.com or call 1300 421 069.

Visit x42monitoring.com

X42 Monitoring is powered by Kangaroo Kick Tech Pty Ltd.

Document status: FRAMEWORK — all amber-highlighted placeholder items require completion with hardware specifications and site-specific details before issue to technicians.